Voltage Regulator General Troubleshooting | ||||
Common malfunctions | fault phenomenon | cause of issue | Maintenance method | |
1. The voltage regulator has no output | input voltage is normal , the meter does not light up , and there is no output | 1. The air switch is open (no power) | Replace the air switch | |
2. The switching power supply board does not work (no DC12V output) | Replace the switching power supply and check whether there is a short circuit in the 12V current | |||
3. Input and output relays do not pull in | Check if the control board is working , or if the relay itself is a problem | |||
input voltage is normal , the meter head is on, and there is no output | show error code | (E-1) No input sampling | Check whether the input sampling line is in poor contact | |
(E-2) No output sampling | Check whether the output sampling line is in poor contact | |||
(E-5) Overload Protection | The load exceeds the rated load and can be recovered by restarting | |||
(---) Overvoltage protection Overvoltage light flashes | Input voltage exceeds rated voltage | |||
(---) Over temperature protection Over temperature bar full | temperature drop can be recovered | |||
Display input voltage flashing | bad temperature sensor | |||
2. The voltage stabilizer does not take the load | The voltage regulator is powered on normally , and the output voltage with load is low | 1. The power terminals are in poor contact, or use aluminum wires (causing loose terminals) | Use copper wire for reliable wiring | |
2. The input power line is too thin (cannot meet the output load power) | Replace the corresponding power cord | |||
3. Check whether the shift relay is damaged | Replace the relay | |||
4. Transformer burned out | Transformer black , leakage | 1. Over rated power to work with load | Check the transformer for damage | |
2. The cooling fan does not rotate | Replace the cooling fan | |||
3. The working temperature is too high | Check the temperature sensor for damage | |||
4. Poor circuit contact leads to burnout | Check the wiring for poor contact | |||
5. The relay shift is incorrect | Check the control board for damage | |||
3. The voltage regulator relay is damaged | Relays are not durable | 1. Check whether the transformer is damaged | Replace the transformer | |
2. The relay models are different, and they often spark during use | Replace the same type of relay |